Troubleshooting Your ICDJ: A Step-by-Step Guide
1. Introduction: The Importance of ICDJ Troubleshooting
In the realm of railway locomotive maintenance, a common challenge encountered by technical personnel is the inability to close the main circuit breaker, often referred to as the DJ (Disjoncteur). This issue is frequently denoted by the acronym ICDJ, which, in the context of locomotive troubleshooting, most likely stands for Impossible to Close the DJ
The Disjoncteur is a vital component of an electric locomotive's electrical system. It acts as the primary circuit breaker, establishing the connection between the locomotive's internal electrical systems and the external power source, which is typically an overhead catenary or a third rail
2. Safety Relay Troubleshooting (2.1)
Safety relays play a critical role in protecting the intricate electrical systems of a locomotive. These devices, including QLM, QOP 1 & 2, QOA, and QRSI-1&2, are specifically designed to detect various abnormal conditions or faults within the system
One of the initial steps in troubleshooting an ICDJ issue involves checking the targets on these safety relays. Each relay is equipped with a target that indicates its operational status. If a safety relay has detected a fault and tripped, its target will be in a "dropped" condition. A dropped target serves as a visual indicator that the relay has been activated due to an identified problem in the system. Should any of the safety relay targets be found in a dropped condition, it signifies that a fault has indeed been detected by that particular relay. In such a scenario, the immediate course of action is to investigate and rectify the specific fault that caused the relay to trip before any attempt is made to close the DJ. This investigation might involve a thorough examination of the electrical circuits and components associated with the tripped relay to identify any abnormalities or malfunctions
If, upon inspection, all the safety relay targets are found to be in their normal (not dropped) condition, it indicates that no major faults have been detected by these primary protective devices. In this case, the troubleshooting process should proceed to the next set of checks. As a basic maintenance measure, it is also recommended to gently tap each of the safety relays and operate their knobs. This simple action can help to ensure that the relay's internal contacts are not stuck or jammed due to dust, corrosion, or mechanical issues, and that the mechanical components of the relay are moving freely and functioning correctly. This step helps to rule out any obvious mechanical impediments within the safety relays themselves.
The following table summarizes the functions of the key safety relays mentioned:
Relay Abbreviation | Relay Name | Function |
---|---|---|
QLM | Main overload relay | Provides overload protection for the main transformer in case of failure |
QOP | Main earth fault relay | Detects earth faults in the main traction circuit |
QOA | Earth fault relay for auxiliaries | Provides earth fault protection for auxiliary equipment |
QRSI | Silicon rectifier overload relay | Prevents overload of the silicon rectifiers |
3. BA Voltage Issues (2.2)
The Battery Voltage, often referred to as BA Voltage, is a critical parameter for the proper functioning of an electric locomotive. It serves as the primary power source for the locomotive's control circuits, including the essential circuits that govern the operation of the DJ
3.1 If BA Voltage showing zero (2.2.1)
When the BA Voltage indicator shows zero, it signifies a complete absence of power from the locomotive's battery system. The first step in this scenario is to check the pilot lamps by unlocking the BL key. The BL key likely refers to a Battery Lock key, and unlocking it should enable the pilot lamps to illuminate if the battery has power. If the pilot lamps also fail to glow, it strongly indicates a fundamental issue with the main battery supply
Following this, the next step involves operating the HBA for 2-3 times. HBA likely stands for Handle Battery switch or a similar control mechanism for the battery circuit. Operating this switch multiple times might help to re-establish an electrical connection if there is a temporary contact problem or a slight oxidation on the switch contacts.
The troubleshooting procedure then directs attention to the Battery MCB (Miniature Circuit Breaker) and the Additional CCBA (likely a Current Carrying Busbar Assembly or a similar protective device), if one is provided near or inside battery box -1. The MCB and CCBA are circuit protection elements designed to prevent overcurrents in the battery system
In the event that the MCB trips again immediately after being reset, or if the Additional CCBA fuse melts again after replacement, it is a clear indication of a persistent fault within the battery circuit that is causing an excessive current draw. In such a situation, the procedure mandates putting the HOBA (likely another High Output Battery switch or a similar main battery control) in the ‘OFF’ position. This step isolates the main battery supply, which is crucial for safety. After isolating the battery, the melted fuse should be replaced with a new one of the correct rating. It is also essential to clear the block section, ensuring that the train is safely stopped and does not obstruct other railway traffic. Finally, the Train Line Controller (TLC) or the appropriate authority must be informed about the situation to coordinate further investigation and assistance.
As a final check in this stage of troubleshooting zero BA Voltage, the technician should open the BA (Battery Assembly or Box) to physically inspect the battery terminals. The inspection should focus on identifying any signs of a cut or open circuit in the wiring connected to the terminals. If any loose or broken connections are found, an attempt should be made to reconnect them if it is feasible and safe to do so.
3.2 If BA voltage is less than 85V (2.2.2)
If the BA Voltage reading is below 85V, it indicates that the battery has some charge but not enough to ensure the reliable operation of all the locomotive's control systems. In this case, the troubleshooting focuses on the Q118 relay. The Q118 relay is an auxiliary protection relay that plays a role in the DJ control circuit, and its proper energization is dependent on having sufficient BA Voltage
The procedure in this scenario is to check if the Q118 relay is energized or not. If it is found to be de-energized, the technician should attempt to close it manually by pressing the BP2 DJ button. BP2 DJ is likely a push button located in the driver's cab that is used to initiate the closing of the DJ. If, after manually closing the Q118 relay and pressing BP2 DJ, the DJ successfully closes, the technician should then resume traction, clear the block section, and inform the TLC about the low BA Voltage and the actions taken. This allows for monitoring of the situation and potential further investigation at a suitable location.
However, if the DJ fails to close even after manually operating the Q118 relay and pressing BP2 DJ, it suggests a more significant underlying issue that is preventing the DJ from closing. In such a case, the troubleshooting guide advises the technician to ask for assistance from the appropriate maintenance personnel or the TLC. This indicates that the problem might be beyond the scope of immediate on-site resolution and requires specialized expertise or equipment. Regular battery maintenance and monitoring of the BA voltage are essential practices to prevent these voltage-related issues and ensure the consistent and reliable operation of the locomotive's electrical systems.
4. RS Pressure Troubleshooting (2.3)
The locomotive's pneumatic system, which provides Reservoir or System Pressure (RS Pressure), is crucial for the operation of various components, including the pantograph and potentially the DJ itself
If the RS pressure is found to be below this threshold, the initial step is to attempt to increase it to the required level. This might involve checking the operation of the air compressors that are responsible for building up the pressure in the system, as well as inspecting any associated controls or valves
However, if the attempt to increase the RS pressure to the required level is unsuccessful, it indicates a potential malfunction within the locomotive's pneumatic system. In such a case, the troubleshooting guide directs the technician to consult page No. 14 for further, more detailed troubleshooting steps that are specific to addressing issues with the pneumatic system
5. Pantograph Issues (2.4)
The pantograph, located on the roof of the electric train, is the apparatus responsible for collecting electrical power from the overhead line
In the context of troubleshooting an ICDJ issue, a lowered pantograph would obviously prevent the locomotive from receiving any electrical power. Since the DJ's function is to connect the locomotive to the power source, attempting to close it when the pantograph is down would be futile. Therefore, the troubleshooting guide explicitly states that if the pantograph is not in the raised condition, the technician should refer to page No. 14 for specific troubleshooting steps related to resolving pantograph issues. This indicates that a separate set of procedures is dedicated to diagnosing and rectifying problems with the pantograph raising and lowering system. Ensuring that the pantograph is correctly raised and making proper contact with the overhead wire is a fundamental prerequisite for the successful operation of the DJ and the subsequent powering of the locomotive.
6. Switch Troubleshooting (BLDJ, BLRDJ, BP1DJ, BP2DJ) (2.5)
The locomotive's control system incorporates various switches that play specific roles in the sequence of operations, including the closing of the DJ. The troubleshooting guide identifies several key switches: BLDJ, BLRDJ, BP1DJ, and BP2DJ
The first switch mentioned is BLDJ, which likely stands for Battery/Brake Line Disconnect for the DJ or a similar control for the Main Circuit Breaker
Next, the guide mentions BP1 DJ, which should initially be in the released position. This suggests that BP1 DJ might be an enabling switch that needs to be disengaged before the closing sequence can be initiated. The procedure then instructs the technician to operate BP1DJ 2-3 times and try to close the DJ. This action might engage a specific part of the DJ closing mechanism or reset an interlock.
Finally, the guide directs the technician to try to close the DJ by pressing BLRDJ/BP2DJ. These are likely the primary push buttons or switches that directly initiate the command for the DJ to close
7. GR Troubleshooting (2.6)
The term GR in this context likely refers to the Gear Regulator or Governor Regulator, a component that controls the locomotive's traction power output. When attempting to close the DJ, it is crucial that the GR is in the ‘0’ position, indicating that there is no demand for traction power
If the GR is not at ‘0’ or if the LSGR is not glowing as expected, the troubleshooting procedure involves manually operating the GR from position 0 to 10 and then back from 10 to 0. This manual cycling of the GR might help to ensure that the mechanism is fully reset to the zero position and that any internal contacts or sensors are correctly aligned.
In addition to checking the GR position, the technician should also check the SMGR drum indicator. SMGR likely stands for Servo Motor Gear Regulator or a similar component that provides a visual indication of the GR's position. This indicator should also show ‘0’ to confirm that the GR is indeed in the zero position. If both the SMGR drum indicator shows ‘0’ and the LSGR is glowing, it provides a strong indication that the GR is correctly set. At this point, the technician should then attempt to close the DJ.
8. Q118 Relay Troubleshooting (2.7)
The Q118 relay is an auxiliary protection relay in the locomotive's electrical system. Its primary function is to monitor the health and proper functioning of various auxiliary equipment and to trip the DJ in the event of a failure in any of these auxiliary systems
8.1 If Q118 is de-energised (2.7.1)
If the Q118 relay is not energized, the first step is to check the status of several contactors: C118, C105, C106, and C107. These contactors are likely associated with the auxiliary circuits that are monitored by the Q118 relay
After checking and operating the contactors, the next step is to manually operate the Q118 relay itself, along with the Q44 and Q46 relays, for 2-3 times each. This manual intervention can help to overcome any temporary sticking or binding within the relays' mechanisms
8.2 If not successful (2.7.2)
If the DJ still fails to close after the steps outlined in section 2.7.1, the troubleshooting guide provides further instructions. The first of these involves putting the BLVMT (likely a Blower Motor Test switch or similar) in the ‘ON’ position. Then, the technician should manually press and hold the Q 118 relay while simultaneously pressing the BP2DJ button to try and close the DJ. If the DJ closes successfully, BP2DJ should be released after 4 seconds, and the manual pressure on Q 118 should be released after 15 seconds. This specific timing might be necessary to allow certain circuits to stabilize or auxiliary equipment to start up
If the DJ closes using this method but then de-energizes again after releasing Q 118, the procedure allows for a temporary measure: wedging the Q 118 relay in the energized condition. This action bypasses the relay's normal operation and its safety monitoring functions. If Q118 is wedged, the technician should then clear the block section, ensuring the train is safely moved. However, while doing so, it is crucial to keep a sharp watch on the concerning auxiliary motors and the status of the C118 contactor. Any abnormal behavior, such as overheating or failure to open, should be noted. The TLC must also be informed that Q118 has been wedged. Wedging a safety-related component should only be considered a temporary measure to move the train to a safer location or clear the line, and it must be done with extreme caution and awareness of the potential risks. Snippets
The troubleshooting guide also includes a note specific to locomotives with microprocessor controls. If any blower contactor is wedged in such a locomotive, the concerned switch should be put in position ‘3’ before attempting to close the DJ. Furthermore, if a blower contactor is wedged, the operation of the corresponding blower motor should be checked frequently to ensure it is functioning correctly and not overheating.
9. CCDJ Fuse Troubleshooting (2.8)
The CCDJ fuse, which likely stands for Circuit Breaker Control DJ fuse, is a crucial protective element within the DJ control circuit
The first step in troubleshooting a potential CCDJ fuse issue is to physically check the fuse to see if it is melted or has blown. If the fuse is indeed found to be melted, it must be replaced with a new fuse of the correct rating, following the established replacement procedure. It is also important to ensure that the fuse is tightened properly in its holder to maintain a good electrical connection.
If the newly replaced CCDJ fuse melts again immediately, it indicates a persistent overcurrent condition in the circuit. In such a case, the troubleshooting guide advises putting the HOBA (High Output Battery switch) in the ‘OFF’ position. This isolates the main battery supply from the DJ control circuit. With the HOBA off, another new CCDJ fuse should be installed to see if the fault is originating from a different part of the system.
If the CCDJ fuse continues to melt even with the HOBA in the ‘OFF’ position, it suggests a more serious short circuit or fault within the DJ control circuit itself. To further isolate the problem, the procedure then recommends trying to energize the locomotive from the rear cab. This action can help to determine if the fault lies in the wiring or components of the front cab's control system.
If, despite trying to energize from the rear cab, the CCDJ fuse still melts, it indicates that the fault is likely located in a part of the DJ control circuit that is common to both cabs. At this point, the troubleshooting guide advises the technician to ask for assistance from the TLC, as the problem might require more specialized diagnostic tools or expertise. Repeated melting of a fuse is a strong indicator of an underlying electrical fault that needs to be identified and rectified to prevent further damage or potential hazards.
10. Q45 Relay Troubleshooting (2.9)
The Q45 relay is an important component in the DJ control circuit, often referred to as the DJ resetting relay and GR-0 ensuring relay
To troubleshoot issues related to Q45, the first step is to ensure that the BLDJ switch is turned ‘ON’ and then press the BP2DJ button. While doing so, the technician should observe whether the Q45 relay energizes or not. This can usually be determined by listening for a click sound or by checking for an indicator light on the relay.
If the Q45 relay fails to energize under these conditions, the troubleshooting guide suggests manually pressing the Q45 relay and releasing it within 4 seconds after the DJ closes (if it does close). This manual operation might help to overcome a temporary mechanical issue, such as sticking contacts within the relay, or it could serve as a way to temporarily bypass a condition preventing its normal energization
11. Q44 Relay Troubleshooting (2.10)
The Q44 relay, often called the Transmission Relay and RGR Protection Relay, is another critical component in the locomotive's electrical system
If the Q44 relay does not energize under these expected conditions, the first troubleshooting step is to operate the relay manually for 2 to 3 times. This manual operation can help to identify and potentially resolve any mechanical jamming or sticking within the relay's mechanism
If the manual operation does not lead to the energization of Q44, the next step is to operate the GR (Gear Regulator) from position 0 to 10 and then back to 10 to 0, and then try to close the DJ. This cycling of the GR might help to reset an interlock or a specific condition that is preventing the Q44 relay from energizing
If all these steps are unsuccessful in energizing the Q44 relay and allowing the DJ to close, the troubleshooting guide advises asking for assistance from qualified personnel. This suggests that the issue might be more complex and require further investigation.
It is crucial to note that the troubleshooting guide explicitly warns that Q44 should not be wedged under any circumstances
12. C118 Contactor Troubleshooting (2.11)
The C118 contactor is an electromagnetic switch that plays a role in the locomotive's auxiliary systems, often involved in providing the starting phase to the ARNO (Auxiliary Rotating Noiseless Output) motor
12.1 If C118 not closing (2.11.1)
If the C118 contactor fails to close under these conditions, the first step is to put the HBA (Handle Battery switch) in the off position and then operate the Q 45 and QCVAR (likely Q Contactor Variable Arno Regulator) relays for 2 – 3 times each. This might help to reset the contacts of these relays, which are part of the control circuit for C118.
Next, with the HBA still in the ‘OFF’ condition, the technician should manually operate the C118 armature 2 - 3 times. This checks for any mechanical sticking or binding within the contactor itself. After this manual operation, an attempt should be made to close the DJ.
If the C118 contactor still does not close, the troubleshooting guide suggests trying to energize the locomotive from the rear cab. This could help to bypass a potential fault in the control wiring or components located in the front cab.
If C118 remains non-operational after all these steps, the technician is advised to ask for assistance, indicating that the problem likely requires more specialized attention.
12.2 If C118 closing (2.11.2)
In a somewhat counterintuitive scenario, the guide also provides steps to follow if the C118 contactor is indeed closing. In this case, the first action is to put the HBA in the ‘OFF’ position, then manually operate the C118 contactor for 2 – 3 times, and subsequently try to close the DJ. The purpose of this step might be to ensure the contactor's proper mechanical movement without electrical power.
If the DJ still does not close after these steps, the guide reiterates the importance of ensuring that the RS pressure is at the required level of 8Kg/Cm2. Assuming the pressure is adequate, the next step involves putting the HQOA, HQOP-1 & HQOP-2 switches to the ‘OFF’ position. These likely stand for High Quality Overload Auxiliary and High Quality Overload Protection - 1 & 2, and they are related to the protection of auxiliary circuits. If the DJ closes successfully after turning these switches off, the technician should proceed with caution, working the train while keeping a close watch on the Traction/Aux Power circuit for any signs of smoke or burning smell, which would indicate a potential fault in one of these auxiliary systems.
If the DJ still does not close, the guide advises trying to energize the locomotive from the rear cab once more. If this attempt is also unsuccessful, the next step is to drain the MR (Main Reservoir) and RS pressure to zero and then re-energize the system. This might help to reset any pneumatic or electro-pneumatic components that could be contributing to the issue.
Finally, if all these measures fail to resolve the problem and the DJ remains closed, the technician should ask for assistance.
13. QUICK TROUBLE SHOOTING IN BLOCK SECTION
14. Conclusion: Prioritizing Safety
Troubleshooting an ICDJ condition in a railway locomotive requires a systematic approach, careful observation, and adherence to safety protocols. This guide has outlined a step-by-step procedure to diagnose and address common issues that might prevent the main circuit breaker (DJ) from closing. By meticulously checking safety relays, battery voltage, pneumatic pressure, pantograph status, control switches, gear regulator position, auxiliary relays and contactors, and protective fuses, technicians can effectively identify and resolve many of the potential causes of an ICDJ.
Throughout this process, safety must remain the paramount concern. Any troubleshooting procedure on railway equipment should only be undertaken after ensuring the locomotive is properly secured and all relevant safety regulations are strictly followed. Technicians must be aware of potential electrical and mechanical hazards and take appropriate precautions to mitigate risks.
It is equally important to recognize the limitations of on-site troubleshooting. When the outlined steps fail to resolve the issue, or when the troubleshooting guide explicitly instructs to do so, seeking assistance from qualified personnel, such as the Train Line Controller or other designated authorities, is crucial. Attempting to force or bypass safety mechanisms without a thorough understanding of the system can lead to dangerous situations, further damage to the equipment, and potentially severe consequences. The information provided in this guide is intended to empower technicians with the knowledge to address common ICDJ issues safely and efficiently, but it should not replace comprehensive training and adherence to established railway maintenance protocols.